PS-3650A/PS-3651A Series Hardware Manual
3-24
3.3.3 Grounding
This section describes the precautions for grounding the PS-A unit.
When supplying power to the PS-A unit, be sure to
separate the input/output and power lines, as shown.
[diagram (a)]
If exclusive grounding is not possible, use a common
connection point. [diagram (b)]
3.3.4 I/O Signal Line Placement
Input and output signal lines must be separated from the power control cables for operating circuits.
If this is not possible, use a shielded cable and ground the edge of the shield.
Do not use common grounding, since it can lead to an accident or machine breakdown.
Check that the grounding
resistance is 100or less.
FG and SG terminals are
internally connected in the PS-A
unit. When connecting an
external device to the PS-A unit
using the SG terminal, be sure
to check that no short-circuit
loop is created when you setup
the system.
The grounding wire should have
a cross sectional area of 2mm
2
or greater. Create the
connection point as close to the
PS-A unit as possible, and make
the wire as short, as possible.
When using a long grounding
wire, replace the thin wire with a
thicker wire, and place it in a
duct.
If the equipment does not function properly when grounded, disconnect the ground wire from the FG
terminal.
(a) Exclusive Grounding (BEST)
(b) Common Grounding (OK)
(c)Common Grounding (Not OK)
PS-A Unit Other
Equipment
PS-A Unit Other
Equipment
PS-A Unit Other
Equipment