The figure shows the group and the signal names of the terminal blocks:
Connecting the Power Cord
Follow these instructions when supplying power to the unit:
When the frame ground (FG) terminal is connected, verify the wire is grounded. Not
grounding the unit can result in excessive Electromagnetic Interference (EMI).
Grounding is required to meet EMC level immunity.
The shield ground (SG) and FG terminals are connected internally in the unit.
Remove power before wiring to the power terminals of the unit.
The unit uses 24 Vdc power. Using any other level of power can damage both the
power supply and the unit.
Since the unit is not equipped with a power switch, connect a power switch to the unit’s
power supply.
Field wiring terminal marking for wire type (75° C (167F) copper conductors only).
Pin Arrangement Group Pin Signal
Name
Group Pin Signal
Name
Fast
Input/Standard
Input
C1 I0 Fast
Input/Standard
Input
D1 IC0
C2 I1 Standard Input D2 I2
Standard Input C3 I3 D3 IC1
C4 I5 D4 I4
C5 I7 D5 I6
C6 I9 D6 I8
C7 I11 D7 I10
Temperature
Input
C8 MS0+ Temperature
Input
D8 MS0-
C9 EX0+ D9 EX0-
C10 MS1+ D10 MS1-
C11 EX1+ D11 EX1-
Analog Input C12 IV0 Analog Input D12 AIC
C13 IV1 D13 IA0
C14 IA1 Analog Output D14 AOC
Analog Output C15 U/I0 D15 U/I1