LT3000 Series Hardware Manual
4-10
4.2.2 Connecting the Power Supply
This section describes the precautions for supplying a power voltage.
If the supplied voltage exceeds the LT unit’s range,
connect a constant voltage transformer.
For between the line and ground, select a power supply
that is low in noise. If there is an excess amount of noise,
connect a insulating transformer.
When supplying power to the LT unit, be sure to
separate the input/output and power lines, as shown.
To increase the noise resistance quality of the power
cord, simply twist each power wire before attaching the
Ring Terminal.
The power supply cable must not be bundled or
positioned close to main circuit lines (high voltage, high
current), or input/output signal lines.
Connect a lightening surge absorber, as shown in the
diagram, to deal with power surges.
To avoid excess noise, make the power cord as short as
possible.
24V DC input unit is must be used with a Class 2 power
supply.
SEE
Chapter 2 Specifications (page 2-1)
Use constant voltage and
insulating transformers with
capacities exceeding Power
Consumption value.
Be sure to ground the surge
absorber (E1) separately from the
LT unit (E2).
Select a surge absorber that has
a maximum circuit voltage greater
than that of the peak voltage of
the power supply.
LT
LT Power
Input/Output
Power
Main Power
LT
Main Circuit
Lightening Surge
Absorber
LT
E2
FG
E1
Constant
Voltage
Transformer
Twisted-pair cord
LT
FG
I
nsulating
Transformer
T2
T1
Twisted-pair cord
LT
FG
Input/Output
Unit
Main
Power
LT
Power
Input/
Output
Power
Input/Output
Unit
Input/Output
Unit
Operation
Unit